VIPE LARISSA (U-2515)
DESIGN DETAILS
DESIGN CODEΕΝ 1776
DESIGN PRESSURE70 barg
DESIGN TEMPERATURE-24 ºC / +60 ºC
MINIMUM / MAXIMUM INLET PRESSURE35 barg / 66,4 barg
MINIMUM / MAXIMUM OUTLET PRESSURE9 barg /-
MINIMUM / MAXIMUM INLET TEMPERATURE+5 ºC / +25 ºC
MINIMUM / MAXIMUM OUTLET TEMPERATURE
OPERATING PRESSURE16,7 barg
OPERATING TEMPERATURE
DESIGN CAPACITY10000 Nm3/h
METERING SKID DESIGN CAPACITY10000 Nm3/h
 
METERING INFRASTRUCTURE
METER TYPETurbine meter
NUMBER OF INSTALLED METERING SKIDS2
NUMBER OF INSTALLED CHROMATOGRAPHS
AUXILIARY EQUIPMENT TOTAL PROBABLE ERRORP=±0,25%, T=±0,3οC
ENERGY UNCERTAINTY±1,15%
 
INSTALLATION DETAILS
METERS CAPACITYG 400
METERS DIAMETER150 mm
METERING SKID DIAMETER
FLOW STRAIGHTENER DESIGN