TRIPOLIS STATION (U-7270) |
DESIGN DETAILS |
DESIGN CODE | ΕΝ 1594, EN ISO 3183 |
DESIGN PRESSURE | 80 barg |
DESIGN TEMPERATURE | -20 ºC / +60 ºC |
MINIMUM / MAXIMUM INLET PRESSURE | 25 barg / 75 barg |
MINIMUM / MAXIMUM OUTLET PRESSURE | 9 barg / – |
MINIMUM / MAXIMUM INLET TEMPERATURE | +6 ºC / +25 ºC |
MINIMUM OUTLET TEMPERATURE | – 5 ºC |
OPERATING PRESSURE | 16,7 barg |
OPERATINING TEMPERATURE | – |
DESIGN CAPACITY | 20000 Nm3/h |
METERING SKID DESIGN CAPACITY | 20000 Nm3/h |
|
METERING INFRASTRACTURE |
METER TYPE | TURBINE FLOW METERS |
NUMBER OF INSTALLED METERING SKIDS | 2 |
NUMBER OF INSTALLED CHROMATOGRAPHS | – |
AUXILIARY EQUIPMENT TOTAL PROPABLE ERROR | P=±0,15%, T=±0,14OC |
ENERGY UNCERTAINTY | ±0,85% |
|
INSTALLATION DETAILS |
METERS CAPACITY | G1000 |
METERS DIAMETER | DN 150 |
METERING SKID DIAMETER | DN 150 |
FLOW STRAIGHTENER DESIGN | – |