| TRIKALA (U-6260) |
| DESIGN DETAILS |
| DESIGN CODE | ANSI B31.8 |
| DESIGN PRESSURE | 80 barg |
| DESIGN TEMPERATURE | -20 ºC / +80 ºC |
| MINIMUM / MAXIMUM INLET PRESSURE | – |
| MINIMUM / MAXIMUM OUTLET PRESSURE | 9 barg / 19 barg |
| MINIMUM / MAXIMUM INLET TEMPERATURE | +6 ºC / +25 ºC |
| MINIMUM / MAXIMUM OUTLET TEMPERATURE | – |
| OPERATING PRESSURE | 16,7 barg |
| OPERATING TEMPERATURE | – |
| DESIGN CAPACITY | 17800 Nm3/h |
| METERING SKID DESIGN CAPACITY | 17800 Nm3/h |
| |
| METERING INFRASTRUCTURE |
| METER TYPE | Turbine meter |
| NUMBER OF INSTALLED METERING SKIDS | 2 |
| NUMBER OF INSTALLED CHROMATOGRAPHS | – |
| AUXILIARY EQUIPMENT TOTAL PROBABLE ERROR | P=±0,15%, T=±0,14οC |
| ENERGY UNCERTAINTY | ±0,38% |
| |
| INSTALLATION DETAILS |
| METERS CAPACITY | G 650 |
| METERS DIAMETER | 150 mm |
| METERING SKID DIAMETER | 150 mm |
| FLOW STRAIGHTENER DESIGN | – |