| PPC LAVRIO (U-3430) |
| DESIGN DETAILS |
| DESIGN CODE | ASME VIII Div.1 |
| DESIGN PRESSURE | 40 barg |
| DESIGN TEMPERATURE | -10 ºC / +80 ºC |
| MINIMUM / MAXIMUM INLET PRESSURE | 26,5 barg / 37,5 barg |
| MINIMUM / MAXIMUM OUTLET PRESSURE | 25 barg / 40 barg |
| MINIMUM / MAXIMUM INLET TEMPERATURE | +3 ºC / +26 ºC |
| MINIMUM / MAXIMUM OUTLET TEMPERATURE | +3 ºC / +26 ºC |
| OPERATING PRESSURE | – |
| OPERATING TEMPERATURE | – |
| DESIGN CAPACITY | 240000 Nm3/h |
| METERING SKID DESIGN CAPACITY | 80000 Nm3/h |
| ULTRASONIC METERING SKID DESIGN CAPACITY | 19000 Νm3/h |
| |
| METERING INFRASTRUCTURE |
| METER TYPE | Four (4) Orifice metersTwo (2) Ultrasonic meters |
| NUMBER OF INSTALLED METERING SKIDS | 4+2 |
| NUMBER OF INSTALLED CHROMATOGRAPHS | 2 |
| METERING EQUIPMENT TOTAL PROBABLE ERROR | P=±0,15%, ΔP=±0,15%, T=±0,14οC |
| ENERGY UNCERTAINTY | ±0,65% |
| |
| INSTALLATION DETAILS |
| METERS CAPACITY | – |
| METERS DIAMETER | 150 mm |
| METERING SKID DIAMETER | 250 mm |
| FLOW STRAIGHTENER DESIGN | ISO 5167 Z3433 |