PPC LAVRIO (U-3430) |
DESIGN DETAILS |
DESIGN CODE | ASME VIII Div.1 |
DESIGN PRESSURE | 40 barg |
DESIGN TEMPERATURE | -10 ºC / +80 ºC |
MINIMUM / MAXIMUM INLET PRESSURE | 26,5 barg / 37,5 barg |
MINIMUM / MAXIMUM OUTLET PRESSURE | 25 barg / 40 barg |
MINIMUM / MAXIMUM INLET TEMPERATURE | +3 ºC / +26 ºC |
MINIMUM / MAXIMUM OUTLET TEMPERATURE | +3 ºC / +26 ºC |
OPERATING PRESSURE | – |
OPERATING TEMPERATURE | – |
DESIGN CAPACITY | 240000 Nm3/h |
METERING SKID DESIGN CAPACITY | 80000 Nm3/h |
ULTRASONIC METERING SKID DESIGN CAPACITY | 19000 Νm3/h |
|
METERING INFRASTRUCTURE |
METER TYPE | Four (4) Orifice metersTwo (2) Ultrasonic meters |
NUMBER OF INSTALLED METERING SKIDS | 4+2 |
NUMBER OF INSTALLED CHROMATOGRAPHS | 2 |
METERING EQUIPMENT TOTAL PROBABLE ERROR | P=±0,15%, ΔP=±0,15%, T=±0,14οC |
ENERGY UNCERTAINTY | ±0,65% |
|
INSTALLATION DETAILS |
METERS CAPACITY | – |
METERS DIAMETER | 150 mm |
METERING SKID DIAMETER | 250 mm |
FLOW STRAIGHTENER DESIGN | ISO 5167 Z3433 |