Emergency Call
.
PPC LAVRIO (U-3430)
DESIGN DETAILS
DESIGN CODEASME VIII Div.1
DESIGN PRESSURE40 barg
DESIGN TEMPERATURE-10 ºC / +80 ºC
MINIMUM / MAXIMUM INLET PRESSURE26,5 barg / 37,5 barg
MINIMUM / MAXIMUM OUTLET PRESSURE25 barg / 40 barg
MINIMUM / MAXIMUM INLET TEMPERATURE+3 ºC / +26 ºC
MINIMUM / MAXIMUM OUTLET TEMPERATURE+3 ºC / +26 ºC
OPERATING PRESSURE
OPERATING TEMPERATURE
DESIGN CAPACITY240000 Nm3/h
METERING SKID DESIGN CAPACITY80000 Nm3/h
ULTRASONIC METERING SKID DESIGN CAPACITY19000 Νm3/h
 
METERING INFRASTRUCTURE
METER TYPEFour (4) Orifice metersTwo (2) Ultrasonic meters
NUMBER OF INSTALLED METERING SKIDS4+2
NUMBER OF INSTALLED CHROMATOGRAPHS2
METERING EQUIPMENT TOTAL PROBABLE ERRORP=±0,15%, ΔP=±0,15%, T=±0,14οC
ENERGY UNCERTAINTY±0,65%
 
INSTALLATION DETAILS
METERS CAPACITY
METERS DIAMETER150 mm
METERING SKID DIAMETER250 mm
FLOW STRAIGHTENER DESIGNISO 5167 Z3433