Emergency Call
.
PPC ALIVERI (U-6370)
DESIGN DETAILS
DESIGN CODEANSI B31.8
DESIGN PRESSURE70 barg
DESIGN TEMPERATURE-20 ºC / +60 ºC
MINIMUM / MAXIMUM INLET PRESSURE26 barg / 66,4 barg
MINIMUM / MAXIMUM OUTLET PRESSURE25 barg / –
MINIMUM / MAXIMUM INLET TEMPERATURE+5 ºC / +24 ºC
MINIMUM / MAXIMUM OUTLET TEMPERATURE+5 ºC / +24 ºC
OPERATING PRESSURE35 barg
OPERATING TEMPERATURE+15 ºC
DESIGN CAPACITY160000 Nm3/h
METERING SKID DESIGN CAPACITY160000 Nm3/h
 
METERING INFRASTRUCTURE
METER TYPEUltrasonic meter
NUMBER OF INSTALLED METERING SKIDS2
NUMBER OF INSTALLED CHROMATOGRAPHS2
AUXILIARY EQUIPMENT TOTAL PROBABLE ERRORP=±0,15%, T=±0,14οC
ENERGY UNCERTAINTY±0,42%
 
INSTALLATION DETAILS
METERS CAPACITY12300 m3/h
METERS DIAMETER381 mm
METERING SKID DIAMETER381 mm
FLOW STRAIGHTENER DESIGNbundle of tubes