Emergency Call
.
NEA MESIMVRIA (U-6910)
DESIGN DETAILS
DESIGN CODEΕΝ1594
DESIGN PRESSURE95 barg
DESIGN TEMPERATURE-24 ºC / +80 ºC
MINIMUM / MAXIMUM INLET PRESSURE50 barg / 93 barg
MINIMUM / MAXIMUM OUTLET PRESSURE
MINIMUM / MAXIMUM INLET TEMPERATURE+6 ºC / +24 ºC
MINIMUM / MAXIMUM OUTLET TEMPERATURE
OPERATING PRESSURE
OPERATING TEMPERATURE
DESIGN CAPACITY417000 Nm3/h
METERING SKID DESIGN CAPACITY208500 Nm3/h
 
METERING INFRASTRUCTURE
  METER (EQUIPMENT) TYPESix (6) Ultrasonic meters one (1) Ultrasonic meter for the station’s by-pass metering skid
NUMBER OF INSTALLED METERING SKIDS3
NUMBER OF INSTALLED CHROMATOGRAPHS3
AUXILIARY EQUIPMENT TOTAL PROBABLE ERRORP=±0,15%, T=±0,14οC
ENERGY UNCERTAINTY±0,46%
 
INSTALLATION DETAILS
ULTRASONIC CAPACITYALTOSONIC V12 – 12” – 4700 m3/h
METER DIAMETER300 mm
METERING SKID DIAMETER300 mm
FLOW STRAIGHTNER DESIGNMin 30 X DN