Emergency Call
.
LARISSA NORTH (U-2520)
DESIGN DETAILS
DESIGN CODEANSI B31.8
DESIGN PRESSURE70 barg
DESIGN TEMPERATURE-15 ºC / +50 ºC
MINIMUM / MAXIMUM INLET PRESSURE45,4 barg / 66,4 barg
MINIMUM / MAXIMUM OUTLET PRESSURE9 barg /-
MINIMUM / MAXIMUM INLET TEMPERATURE+8 ºC / –
MINIMUM / MAXIMUM OUTLET TEMPERATURE+3 ºC / –
OPERATING PRESSURE16,7 barg
OPERATING TEMPERATURE
DESIGN CAPACITY25910 Nm3/h
METERING SKID DESIGN CAPACITY25910 Nm3/h
 
METERING INFRASTRUCTURE
METER TYPETurbine meter
NUMBER OF INSTALLED METERING SKIDS2
NUMBER OF INSTALLED CHROMATOGRAPHS1
AUXILIARY EQUIPMENT TOTAL PROBABLE ERRORP=±0,15%, T=±0,14οC
ENERGY UNCERTAINTY±0,47%
 
INSTALLATION DETAILS
METERS CAPACITYG1000
METERS DIAMETER200 mm
METERING SKID DIAMETER200 mm
FLOW STRAIGHTENER DESIGNISO 5167 Type C, bundle of 19 tubes