Emergency Call
.
LAMIA (U-2620)
DESIGN DETAILS
DESIGN CODEANSI B31.8
DESIGN PRESSURE70 barg
DESIGN TEMPERATURE-24 ºC / +80 ºC
MINIMUM / MAXIMUM INLET PRESSURE35 barg / 66,4 barg
MINIMUM / MAXIMUM OUTLET PRESSURE9 barg / –
MINIMUM / MAXIMUM INLET TEMPERATURE+6 ºC / +25 ºC
MINIMUM / MAXIMUM OUTLET TEMPERATURE
OPERATING PRESSURE16,7 barg
OPERATING TEMPERATURE
DESIGN CAPACITY28000 Nm3/h
SKID DESIGN CAPACITY28000 Nm3/h
 
METERING INFRASTRUCTURE
METER TYPETurbine meter
NUMBER OF INSTALLED METERING SKIDS2
NUMBER OF INSTALLED CHROMATOGRAPHS
AUXILIARY EQUIPMENT TOTAL PROBABLE ERRORP=±0,15%, T=±0,14οC
ENERGY UNCERTAINTY±0,65%
 
INSTALLATION DETAILS
METERS CAPACITYG1000
METERS DIAMETER200 mm
METERING SKID DIAMETER200 mm
FLOW STRAIGHTENER DESIGN