HERONAS (U-6020) |
DESIGN DETAILS |
DESIGN CODE | ANSI B31.8 |
DESIGN PRESSURE | 70 barg |
DESIGN TEMPERATURE | -29 ºC / +80 ºC |
MINIMUM / MAXIMUM INLET PRESSURE | 25,5 barg / 66,4 barg |
MINIMUM / MAXIMUM OUTLET PRESSURE | 25 barg / – |
MINIMUM / MAXIMUM INLET TEMPERATURE | +5 ºC / +24 ºC |
MINIMUM / MAXIMUM OUTLET TEMPERATURE | +5 ºC / +24 ºC |
OPERATING PRESSURE | 45 barg |
OPERATING TEMPERATURE | +10ºC |
DESIGN CAPACITY | 40000 Nm3/h |
METERING SKID DESIGN CAPACITY | 40000 Nm3/h |
|
METERING INFRASTRUCTURE |
METER TYPE | Ultrasonic meter |
NUMBER OF INSTALLED METERING SKIDS | 2 |
NUMBER OF INSTALLED CHROMATOGRAPHS | 2 |
AUXILIARY EQUIPMENT TOTAL PROBABLE ERROR | P=±0,15%, T=±0,14οC |
ENERGY UNCERTAINTY | ±0,51% |
|
INSTALLATION DETAILS |
METERS CAPACITY | 2500 m3/h |
METERS DIAMETER | 200 mm |
METERING SKID DIAMETER | 200 mm |
FLOW STRAIGHTENER DESIGN | – |