Emergency Call
.
HERON B (U-6030)
DESIGN DETAILS
DESIGN CODEANSI B31.8
DESIGN PRESSURE80 barg
DESIGN TEMPERATURE-20 ºC / +80 ºC
MINIMUM / MAXIMUM INLET PRESSURE30,5 barg / 66,4 barg
MINIMUM / MAXIMUM OUTLET PRESSURE30 barg / –
MINIMUM / MAXIMUM INLET TEMPERATURE+5 ºC / +24 ºC
MINIMUM / MAXIMUM OUTLET TEMPERATURE+5 ºC / +24 ºC
OPERATING PRESSURE45 barg
OPERATING TEMPERATURE+10ºC
DESIGN CAPACITY85000 Nm3/h
METERING SKID DESIGN CAPACITY85000 Nm3/h
 
METERING INFRASTRUCTURE
METER TYPEUltrasonic meter
NUMBER OF INSTALLED METERING SKIDS2
NUMBER OF INSTALLED CHROMATOGRAPHS
AUXILIARY EQUIPMENT TOTAL PROBABLE ERRORP=±0,15%, T=±0,14οC
ENERGY UNCERTAINTY±0,51%
 
INSTALLATION DETAILS
METERS CAPACITY7000 m3/h
METERS DIAMETER300 mm
METERING SKID DIAMETER300 mm
FLOW STRAIGHTENER DESIGN