| ATHENS HAR (U-2970) |
| DESIGN DETAILS |
| DESIGN CODE | ASME B31.8 / PED |
| DESIGN PRESSURE | 70 barg |
| DESIGN TEMPERATURE | -15 ºC / +50 ºC |
| MINIMUM / MAXIMUM INLET PRESSURE | 30 barg / 66,4 barg |
| MINIMUM / MAXIMUM OUTLET PRESSURE | 9 barg / 25 barg |
| MINIMUM / MAXIMUM INLET TEMPERATURE | +6 ºC / +25 ºC |
| MINIMUM OUTLET TEMPERATURE | -5 ºC |
| OPERATING PRESSURE | 23,0 barg |
| OPERATING TEMPERATURE | – |
| DESIGN CAPACITY | 30.000 Nm3/h |
| METERING SKID DESIGN CAPACITY | 30.000 Nm3/h |
| |
| METERING INFRASTRUCTURE |
| METER TYPE | Ultrasonic meter |
| NUMBER OF INSTALLED METERING SKIDS | 2 |
| NUMBER OF INSTALLED CHROMATOGRAPHS | – |
| AUXILIARY EQUIPMENT TOTAL PROBABLE ERROR | P=±0,15%, T=±0,14οC |
| ENERGY UNCERTAINTY | ±0,47% |
| |
| INSTALLATION DETAILS |
| METER TYPE | ALTOSONIC V12 – 8” |
| METERS DIAMETER | 200 mm |
| METERING SKID DIAMETER | 200 mm |
| FLOW STRAIGHTENER DESIGN | – |