ATHENS EAST (U-2940)
DESIGN DETAILS
DESIGN CODEANSI B31.8
DESIGN PRESSURE40 barg
DESIGN TEMPERATURE-15 ºC / +50 ºC
MINIMUM / MAXIMUM INLET PRESSURE27,6 barg / 37,7 barg
MINIMUM / MAXIMUM OUTLET PRESSURE9 barg /-
MINIMUM / MAXIMUM INLET TEMPERATURE-2 ºC / +24 ºC
MINIMUM / MAXIMUM OUTLET TEMPERATURE+3 ºC / +11 ºC
OPERATING PRESSURE16,7 barg
OPERATING TEMPERATURE
DESIGN CAPACITY110219 Nm3/h
METERING SKID DESIGN CAPACITY110219 Nm3/h
 
METERING INFRASTRUCTURE
METER TYPETurbine meter
NUMBER OF INSTALLED METERING SKIDS2
NUMBER OF INSTALLED CHROMATOGRAPHS
AUXILIARY EQUIPMENT TOTAL PROBABLE ERRORP=±0,15%, T=±0,14οC
ENERGY UNCERTAINTY±0,47%
 
INSTALLATION DETAILS
METERS CAPACITYG4000
METERS DIAMETER400 mm
METERING SKID DIAMETER400 mm
FLOW STRAIGHTENER DESIGNISO 5167 Type C, bundle of 19 tubes