| AdG III (U-2840) |
| DESIGN DETAILS |
| DESIGN CODE | ΕΝ 1594 / ΕΝ 13480 |
| DESIGN PRESSURE | 80 barg |
| DESIGN TEMPERATURE | -20 ºC / +60 ºC |
| MINIMUM / MAXIMUM INLET PRESSURE | 25 barg / 75 barg |
| MINIMUM / MAXIMUM OUTLET PRESSURE | – |
| MINIMUM / MAXIMUM INLET TEMPERATURE | +6 ºC / +25 ºC |
| MINIMUM / MAXIMUM OUTLET TEMPERATURE | – |
| OPERATING PRESSURE | 16,7 barg |
| OPERATING TEMPERATURE | – |
| DESIGN CAPACITY | 23.500 Nm3/h |
| METERING SKID DESIGN CAPACITY | 23.500 Nm3/h |
| |
| METERING INFRASTRUCTURE |
| METER TYPE | Turbine meter |
| NUMBER OF INSTALLED METERING SKIDS | 2 (1+1) |
| NUMBER OF INSTALLED CHROMATOGRAPHS | – |
| AUXILIARY EQUIPMENT TOTAL PROBABLE ERROR | P=±0,15%, T=±0,14OC |
| ENERGY UNCERTAINTY | ±0,40% |
| |
| INSTALLATION DETAILS |
| METERS CAPACITY | G1000 |
| METERS DIAMETER | 150 mm (6”) |
| METERING SKID DIAMETER | 150 mm (6”) |
| FLOW STRAIGHTENER DESIGN | – |