DESIGN DETAILS
DESIGN CODEΕΝ 1594, EN ISO 3183
DESIGN PRESSURE80 barg
DESIGN TEMPERATURE-20 ºC / +60 ºC
MINIMUM / MAXIMUM INLET PRESSURE25 barg / 75 barg
MINIMUM / MAXIMUM OUTLET PRESSURE9 barg / –
MINIMUM / MAXIMUM INLET TEMPERATURE+6 ºC / +25 ºC
MINIMUM OUTLET TEMPERATURE– 5 ºC
OPERATING PRESSURE16,7 barg
OPERATINING TEMPERATURE
DESIGN CAPACITY20000 Nm3/h
METERING SKID DESIGN CAPACITY20000 Nm3/h
 
METERING INFRASTRACTURE
METER TYPETURBINE FLOW METERS
NUMBER OF INSTALLED METERING SKIDS2
NUMBER OF INSTALLED CHROMATOGRAPHS
AUXILIARY EQUIPMENT TOTAL PROPABLE ERRORP=±0,15%, T=±0,14OC
ENERGY UNCERTAINTY±0,85%
 
INSTALLATION DETAILS
METERS CAPACITYG1000
METERS DIAMETERDN 150
METERING SKID DIAMETERDN 150
FLOW STRAIGHTENER DESIGN