THESSALONIKI EAST (U-2220) |
DESIGN DETAILS |
DESIGN CODE | ANSI B31.8 |
DESIGN PRESSURE | 70 barg |
DESIGN TEMPERATURE | -15 ºC / +50 ºC |
MINIMUM / MAXIMUM INLET PRESSURE | 34,2 barg / 55 barg |
MINIMUM / MAXIMUM OUTLET PRESSURE | 9 barg /- |
MINIMUM / MAXIMUM INLET TEMPERATURE | +6 ºC / +24 ºC |
MINIMUM / MAXIMUM OUTLET TEMPERATURE | +3 ºC / +7 ºC |
OPERATING PRESSURE | 16,7 barg |
OPERATING TEMPERATURE | – |
DESIGN CAPACITY | 145054 Nm3/h |
METERING SKID DESIGN CAPACITY | 72527 Nm3/h |
|
METERING INFRASTRUCTURE |
METER TYPE | Turbine meter |
NUMBER OF INSTALLED METERING SKIDS | 3 |
NUMBER OF INSTALLED CHROMATOGRAPHS | 1 |
AUXILIARY EQUIPMENT TOTAL PROBABLE ERROR | P=±0,15%, T=±0,14οC |
ENERGY UNCERTAINTY | ±0,47% |
|
INSTALLATION DETAILS |
METERS CAPACITY | G2500 |
METERS DIAMETER | 300 mm |
METERING SKID DIAMETER | 300 mm |
FLOW STRAIGHTENER DESIGN | ISO 5167 Type C, bundle of 19 tubes |