KIPI (U-3900) | |
DESIGN DETAILS | |
DESIGN CODE | EN 1776 |
DESIGN PRESSURE | 80 barg |
DESIGN TEMPERATURE | -24 ºC / +80 ºC |
MINIMUM / MAXIMUM INLET PRESSURE | 50 barg / 75 barg |
MINIMUM / MAXIMUM OUTLET PRESSURE | – |
MINIMUM / MAXIMUM INLET TEMPERATURE | +6 ºC / +25 ºC |
MINIMUM / MAXIMUM OUTLET TEMPERATURE | – |
OPERATING PRESSURE | – |
OPERATING TEMPERATURE | – |
DESIGN CAPACITY | 856164 Nm3/h |
METERING SKID DESIGN CAPACITY | 551750 Nm3/h |
METERING INFRASTRUCTURE | |
METER TYPE | Three (3) Turbine meters, three (3) Ultrasonic meters, and one (1) Ultrasonic meter for the Station’s by-pass metering skid |
NUMBER OF INSTALLED METERING SKIDS | 3 |
NUMBER OF INSTALLED CHROMATOGRAPHS | 3 |
METERING EQUIPMENT TOTAL PROBABLE ERROR | P=±0,07%, T=±0,14οC |
ENERGY UNCERTAINTY | ±0,32% |
INSTALLATION DETAILS | |
TURBINE METERS CAPACITY | G10000 |
METERS DIAMETER | 500 mm |
METERING SKID DIAMETER | 500 mm |
BYPASS METERING SKID DIAMETER | 750 mm |
FLOW STRAIGHTENER DESIGN | ISO 5167 |
Note:
Two (2) metering skids can be in operation, while the third one can be in standby mode. Each metering skid includes one (1) turbine meter for invoicing purposes and (1) ultrasonic meter for checking purposes. The Station’s by-pass metering skid includes one (1) ultrasonic meter and one (1) chromatograph and it is activated only in extraordinary situations. The Station’s by-pass metering skid capacity is equal to 70% of the Station’s design capacity.